 Download in PDF form
 Download as a MS Word Document

** NOTE TO SPECIFIER ** Austin Mohawk, Inc.; Prefabricated or factory-built structures.

This section is based on the products of Austin Mohawk Inc., which is located at:  2175 Beechgrove Pl.
  Utica, NY 13501
  Toll Free: (800) 962-4147
  Tel: (315) 793-9390
  Fax: (315) 793-9270
  Email: info@austinmohawk.com
  www.austinmohawk.com

Austin Mohawk, Inc. was created in 2004 with the merging of Austin Fabricating, Inc., (buildings and shelters) and Mohawk Manufacturing, Inc. (canopies), two longtime sister companies. In their respective industries, each was among the oldest and most well respected manufacturers. Together, we expect to bring an even stronger and more integrated product line to our customers.

Austin Mohawk has spent 80+ years building superior quality, prefabricated metal structures. Our product lineup includes buildings, shelters, canopies and our exclusive FrameFast™ Framing System. Prefabricated or factory-built structures have significant advantages over site-built construction—including economy, speed, quality, and flexibility. Our prefabricated metal buildings and booths can be custom built in aluminum or steel. From cashier booths to convenience stores to weigh station buildings, our custom built booths and buildings are modular, functional, and aesthetically pleasing.


SECTION 13129 - PREFABRICATED METAL BUILDINGS AND SHELTERS, Copyright 2005, ARCAT, Inc.

PART 1

1.1 SECTION INCLUDES

** NOTE TO SPECIFIER **  Delete items below not required for project.

A.       Prefabricated Pressbox.

1.2 RELATED SECTIONS

** NOTE TO SPECIFIER **  Delete any sections below not relevant to this project; add others as required.

A.       Section 03300 - Cast-In-Place Concrete: Concrete pad, foundations and anchor bolts.

B.       Section 02870 - Bollards: Metal, concrete and stone bollards.

C.       Section 05500 - Metal Fabrications.

D.       Section 08710 - Door Hardware.

E.       Section 07900 - Joint Sealers.

F.       Division 15 - Plumbing: Plumbing services and connections.

G.       Division 16 - Electrical: Electrical power service and wiring connections.

1.3 REFERENCES

** NOTE TO SPECIFIER **  Delete references from the list below that are not actually required by the text of the edited section.

A.       ASTM A 513 - Standard Specification for Electric-Resistance-Welded Carbon and Alloy Steel Mechanical Tubing.

B.       ASTM A 653/A - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.

C.       ASTM A 1008/A - Standard Specification for Steel Bars, Carbon and Alloy, Cold- Finished.

D.       ASTM B 209 - Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate.

E.       ASTM B 221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes.

F.       ASTM B 632/B 632M - Standard Specification For Aluminum-Alloy Rolled Tread Plate.

G.       ASTM C-578 - Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation.

H.       ASTM C 1048 - Standard Specification for Heat-Treated Flat Glass - Kind Hs, Kind Ft Coated and Uncoated Glass.

I.       ASCE 7 - Minimum Design Loads for Buildings and Other Structures

J.       APA PRP-108 or PFS PRP-133 - Performance Standards and Policies for Structural-Use Panels

K.       ICC/ANSI A117.1 - Accessible and Usable Buildings and Facilities.

L.       NFPA 70 - National Electric Code.

1.4 DESIGN REQUIREMENTS

** NOTE TO SPECIFIER **  Edit as required to suit project requirements. Standard loads are specified below, consult with manufacturer for requirements that exceed those specified as follows.

A.       Provide factory built, prefabricated press box capable of withstanding the effects of gravity loads and the following loads and stresses within limits and under conditions indicated.

B.       Wind Loads:  Determine loads based on the following minimum design wind pressures:

** NOTE TO SPECIFIER **  Select one of the following two paragraphs and delete the one not required.

1.       Uniform pressure of 50 lbf/sq ft, acting inward or outward (standard).

2.       Uniform pressure as indicated on Drawings.

3.       Wind Load:

** NOTE TO SPECIFIER **  Select one of the following two paragraphs and delete the one not required.

a.       Buildings: 120 mph (2000 IBC Exp. C). (standard)

b.       Shelters: 90 mph. (standard)

4.       Snow Loads: 50 lbf/sq ft. (standard)

C.       Seismic Performance:  Provide factory built, prefabricated press box capable of withstanding the effects of earthquake motions determined according to:

1.       ASCE 7, "Minimum Design Loads for Buildings and Other Structures": Section 9, "Earthquake Loads".

D.       Thermal Movements:  Provide factory built, prefabricated press box that allows for thermal movements resulting from the following maximum change (range) in ambient and surface temperatures by preventing buckling, opening of joints, overstressing of components, failure of joint sealants, failure of connections, and other detrimental effects.  Base engineering calculation on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss.

1.       Temperature Change (Range):  120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces.

** NOTE TO SPECIFIER **  Ballistic resistant panels and glazing are optional. Select the ballistic resistant level required from the following paragraphs and delete those not required. Delete if not required.

E.       Electrical Devices: Devices UL listed with wiring bearing UL classification and conforming to the current NEC.

1.5 SUBMITTALS

A.       Submit under provisions of Section 01300.

B.       Product Data:  Manufacturer's data sheets on each product to be used, including:

1.       Construction details, material descriptions, dimensions of individual components and profiles, and finishes.

2.       Preparation instructions and recommendations.

3.       Storage and handling requirements and recommendations.

4.       Installation methods.

** NOTE TO SPECIFIER ** Adherence to applicable state and local codes is the responsibility of the Owner.  The provision of P.E. stamped drawings and/or design approval and inspection for compliance for various states is available from building manufacturer at additional cost.

C.       Shop CAD Drawings: Include plans, elevations, sections, details, and attachments to other work. Adherence to applicable state and local codes is the responsibility of the owner.  The provision of P.E. stamped CAD drawings and/or design approval and inspection for compliance for various states is available from building manufacturer.

D.       Selection Samples:  For each finish product specified, two complete sets of color chips representing manufacturer's full range of available colors and patterns.

E.       Certificates:  Product certificates signed by the manufacturer certifying material compliance with specified performance characteristics and criteria, and physical requirements.

F.       Warranty documents specified herein.

1.6 QUALITY ASSURANCE

A.       Manufacturer Qualifications: Company specializing in manufacturing prefabricated press boxes with a minimum documented experience of ten years.

B.       Design:  All prefabricated press boxes are to be built by a company regularly employing a quality assurance program by an independent third party quality control firm.  The manufacturing process will include a 5-stage, 35-step, quality inspection for each system.

C.       Preinstallation Meetings:  Conduct meetings to verify project requirements, substrate conditions, utility connections, manufacturer's installation instructions, and warranty requirements.  Comply with Division 1 requirements.

1.7 DELIVERY, STORAGE, AND HANDLING

A.       Store products in manufacturer's unopened packaging until ready for installation.

B.       Protect all components and accessories from corrosion, deformation, damage and deterioration when stored at job site.  Keep materials free from dirt and foreign matter.

1.8 PROJECT CONDITIONS

A.       Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results.  Do not install products under environmental conditions outside manufacturer's absolute limits.

1.9 WARRANTY

A.       Provide the manufacturers 5 year limited warranty on anodized aluminum surfaces against oxidation and the manufacturers 20 year limited warranty against peeling, flaking and chipping of deck and fascia when properly maintained.

B.       Provide manufacturer’s warrantees on all accessory items provided such as, but not limited to, air conditioning, lights, and heating units.

PART 2 PRODUCTS

2.1 MANUFACTURERS

A.       Acceptable Manufacturer: Austin Mohawk Inc., 2175 Beechgrove Place, Utica, New York  13501.  ASD. Tel: (315) 793-9390. Fax: (315) 793-9270.  E-mail: info@austinmohawk.com,  Website: austinmohawk.com.

** NOTE TO SPECIFIER **  Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.

B.       Substitutions:  Not permitted.

C.       Requests for substitutions will be considered in accordance with provisions of Section 01600.

2.2 MATERIALS

A.       Aluminum:  Alloy and temper recommended by manufacturer for type of use and finish specified, and as follows:

1.       Sheet:  ASTM B 209.

2.       Extruded Shapes:  ASTM B 221.

3.       Rolled Tread Plate:  ASTM B 632/B 632M, Alloy 6061-T4 or 6061-T6.

B.       Cold-Rolled Steel Sheet:  ASTM A 1008/A, Commercial Steel (CS), Type B.

C.       Zinc-Coated (Galvanized) Steel Sheet:  ASTM A 653/A, commercial quality, G90 (Z275) coating designation; mill phosphatized.

D.       Aluminum Treadplate: Aluminum plate conforming to ASTM B 209.

E.       Steel Mechanical Tubing:  ASTM A 513, welded steel mechanical tubing.

F.       Expanded Polystyrene (EPS) Core: Minimum of .95 pcf complying with ASTM C-578 Type 1.

G.       Oriented Strand Board (OSB):  Standard Grade; minimum physical properties conforming to APA PRP-108.

H.       Clear Tempered Float Glass:  ASTM C 1048, Kind FT, Condition A, Type I, Class 1, Quality q3.

I.       Anchorages:  Anchor bolts, as specified in Section 03300.

2.3 PREFABRICATED ALUMINUM PRESS BOX

A.       Prefabricated all aluminum press box with snap-together extruded 6036-T6 low-maintenance, corrosion-resistant aluminum alloy framing system. All connections internally fastened with no exposed fasteners on building exterior.

1.       Press Box Style:

a.       Varsity – All standard offerings and available accessories

b.       Collegiate - All standard offerings with Camera Deck and available accessories

c.       Division I – (10’ wide only) Two Tier Interior Seating Levels and available accessories

d.       Professional – (10’ wide only )Two Tier Interior Seating Levels, Camera Deck, Anti-Glare Glazing and available accessories

e.       Double Decker – Available in all styles, (Two Tier Seating 10’ wide only)

f.       Press box Over Concession Stand – Available in all styles, (Two Tier Seating 10’ wide only)

2.       Camera Deck:

a.       Camera deck standard 8’ x 12’ with roof hatch, internal ladder, and requisite 42” high perimeter railings with cyclone fence to meet 4” sphere criteria.

b.       Camera deck full length and width with roof hatch, internal ladder, and requisite 42” high perimeter railings with cyclone fence to meet 4” sphere criteria.

c.       WP GFI Receptacle(s) at camera deck level.

** NOTE TO SPECIFIER **** NOTE TO SPECIFIER **  Select the building style required from the following paragraphs and delete those not required. Coordinate custom styles with Austin Mohawk.

3.       Doors:

a.       Sliding door(s) (*standard).

** NOTE TO SPECIFIER **  Select the door types required from the following paragraphs and delete those not required.

b.       Swinging door(s).

c.       6’ typical wide by building width entry platform(s) with railing.

4.       Windows:

** NOTE TO SPECIFIER **  Select the window types required from the following paragraphs and delete those not required.

a.       Horizontal sliding windows (*standard).

b.       2-piece sliding window up to 16’ long.

c.       Fixed windows up to 12’ long.

d.       Anti-glare glass (virtually eliminates window glare).

e.       Tinted glass.

f.       ¼” Low-E.

g.       Insulated Thermal pane.

5.       Roof Type:

a.       Flat Roof, Galvanized interlocking steel pan sections, roof drains into full (4) side perimeter gutter system with downspouts to grade. (*standard).

** NOTE TO SPECIFIER **  Select the roof type required from the following paragraphs and delete those not required.

b.       1) 4” Roof Overhang (*standard)

          2) 6 inch overhang.

          3) 12 inch overhang.

          4) 24 inch overhang.

6.       Entry Platform with Railings:

a.       6’ wide by depth of press box and requisite 42” high perimeter railings with cyclone fence to meet 4” sphere criteria.

7.       Press Box Support Structure:

a.       Structural shapes to meet one of the following ASTM specifications: A36, A36/572 grade 50, A572 grade 50, A529-50, or A500 grade B.

b.       Shop Connections are to be seal welded.

c.       At completion of fabrication all steel components are to be “Hot Dipped” galvanized to ASTM-A-123 specifications.

** NOTE TO SPECIFIER **  Select the size required from the following paragraphs and delete those not required. The maximum shipping width for custom sizes is 16 feet.

B.       Size:

1.       7 feet x 12 feet

2.       7 feet x 16 feet

3.       7 feet x 18 feet

4.       7 feet x 24 feet

5.       7 feet x 30 feet

6.       8 feet x 12 feet

7.       8 feet x 16 feet

8.       8 feet x 18 feet

9.       8 feet x 24 feet

10.       8 feet x 30 feet

11.       8 feet x 36 feet

12.       8 feet x 42 feet

13.       8 feet x 48 feet

14.       8 feet x 60 feet

15.       10 feet x 12 feet

16.       10 feet x 16 feet

17.       10 feet x 18 feet

18.       10 feet x 24 feet

19.       10 feet x 30 feet

20.       10 feet x 36 feet

21.       10 feet x 42 feet

22.       10 feet x 48 feet

23.       10 feet x 60 feet

C.       Height: Nominal outside height of 93 inches (236 mm). Interior floor to ceiling height 83 inches (2108.2 mm) (*standard).

D.       Frame Construction: Provide snap together type structural framing of 6063-T6 aluminum alloy extrusions. Connections shall be fastened internally to framing systems using concealed mechanical fasteners or MIG welded where necessary. Exposed fasteners on building exterior are not acceptable.  Members shall have a manufacturer’s finish as follows: (*standard)

** NOTE TO SPECIFIER **  Select the finish required from the following paragraphs and delete those not required. Custom colors are available at additional cost.

1.       Quaker Bronze.

2.       Austin White.

3.       Clear Anodized finish.

4.       Custom color as selected by the Architect.

E.       Base/Floor: Finished floor of 3/16” nonskid aluminum tread plate. Floor is mounted to 2 inch to 4 inch (51 mm to 102 mm) tube/channel steel base frame (*standard).

1.       3/16” nonskid aluminum tread plate with R-19 expanded polystyrene insulation and 24ga steel underside.

2.       1/8” nonskid aluminum tread plate with 3/4” plywood sub-floor, R-19 expanded polystyrene insulation and 24ga steel underside.

3.       12” x 12” commercial grade vinyl tile, ¼” lauan board, 3/4” sub-floor, R-19 expanded polystyrene insulation and 24ga steel underside.

4.       18-1/8” x 18-1/8” raised disc rubber tile w/ 4” cove base molding, ¼” lauan board, 3/4” sub-floor, R-19 expanded polystyrene insulation and 24ga steel underside.

5.       24” x 24” Mohawk Modular Commercial 1/2” carpet tile with 4” cove base molding ¼” lauan board, 3/4” sub-floor, R-19 expanded polystyrene insulation and 24ga steel underside.

F.       Wall Panel: Overall thickness of panel shall be 3 inches (76.2 mm) with a exterior face of manufacturers standard .032 aluminum, a 3 inch (76.2 mm) insulation core and a .032 interior aluminum face (*standard R-12 thru R-28).

1.       Finish: Interior and exterior panel faces shall have a manufacturer’s finish as follows:

** NOTE TO SPECIFIER **  Select the finish required from the following paragraphs and delete those not required. Custom colors are available at additional cost.

a.       Quaker Bronze.

b.       Austin White.

c.       Clear Anodized finish.

d.       Custom color as selected by the Architect.

e.       5/8” Vinyl coated Gypsum board, color as selected by the architect.

** NOTE TO SPECIFIER **  Ballistic resistant panels and glazing are optional. Select the ballistic resistant level required from the following paragraphs and delete those not required. Delete if not required.

G.       Interior Ceiling Panels:

1.       Prefinished steel, 24 gauge painted white with expanded polystyrene core providing a smooth flat interior. (*standard R-5 thru R-19)

2.       24” x 48” Acoustical Ceiling Tile with typical drop ceiling grid with expanded polystyrene insulation (R-19).

3.       24” x 24” Acoustical Ceiling Tile with typical drop ceiling grid with expanded polystyrene insulation (R-19).

H.       Flat Roof: Galvanized steel, 20 to 24 gauge, G-60 zinc coating, interlocking pan sections, 3 inches (76.2 mm) high varying widths and capable of supporting a minimum 50 psf (1915 Pa) live load. Roof drains into full (4) side perimeter gutter system with downspouts to grade (*standard).

** NOTE TO SPECIFIER **  Select the accessories required from the following paragraphs and delete the items not required. Coordinate the selection of doors and windows with the selections identified in the previous building and shelter paragraphs.

2.4 ACCESSORIES

A.       Sliding Doors:

1.       Horizontal sliding unit with 1/8 inch (3.18 mm) thick, clear tempered safety glass.

2.       Full weather-stripping.

3.       Deadlock:  Mortised, laminated hook bolt type; with removable cylinder capable of being master keyed.

B.       Swinging Doors: 1-3/4 inches (44 mm) thick, tubular-frame design.

1.       36 inch by 80 inch half glass Commercial Grade aluminum swing door.

2.       36 inch by 80 inch all glass Commercial Grade aluminum swing door.

3.       32 inch by 80 inch half glass Extruded aluminum sliding door

4.       36 inch by 80 inch half glass Commercial Grade steel swing door.

5.       Hardware:

** NOTE TO SPECIFIER **  Select the required latching devices from the following paragraphs; delete the items not required. If more that one device is required, identify the location of each on the Drawings.

a.       Latch:

          1) Deadlock, commercial grade aluminum type.

          2) Mortised, laminated bolt type; with push / pull hardware and removable cylinder capable of being master keyed.

          3) Commercial grade steel type, single bore lever handle lockset with keyed entry and thumb turn interior.

          4) Classroom Lockset with Panic Hardware.

b.       Three butt hinges.

c.       Closer.

d.       Full weather-stripping.

6.       Glazing:

a.       1/8 inch (3 mm) thick, clear tempered safety glass.

b.       3/16 inch (4.75 mm) thick, clear tempered safety glass.

c.       1/4" inch (6 mm) thick, clear tempered safety glass.

d.       1/4 inch (6 mm) thick, clear polycarbonate.

e.       3/4 inch (19 mm) thick, insulated, clear tempered safety glass.

** NOTE TO SPECIFIER **  The following paragraph is for use with aluminum buildings only; delete if not required.

C.       Fixed Windows: 1/8 inch (3.18 mm) thick, clear tempered safety glass glazed within wall system extrusions and not fastened to the exterior wall. Glass sealed with concealed gasket system (*standard).

1.       End wall viewing panels for increased field of vision.

** NOTE TO SPECIFIER **  The following paragraph is for use with steel buildings only; delete if not required.

D.       Horizontal Sliding Windows:  Shall have aluminum frame with 1/8 inch (3.18 mm) thick, clear tempered safety glass glazed.  Windows are equipped with insect screen and locking device (*standard).

E.       Optional Custom Windows:

** NOTE TO SPECIFIER **  Select the ballistic resistant level required from the following paragraphs and delete those not required.

1.       Fixed windows up to 12’ long.

2.       2-piece sliding windows up to 16’ long.

3.       Anti-glare glass (fixed only) virtually eliminates window glare.

4.       Glazed within an extruded aluminum exterior stop and an extruded aluminum interior stop which are mechanically fastened to interior face of the window rough openings. Glass sealed with butyl architectural glazing tape.

5.       Full width roll up weather proof security shutters to protect against vandalism. Factory installed, motorized, PVC coated and rebar reinforced.

F.       Electrical Power Service: Provide in accordance with NEC Standards.

1.       Press box shall be of open construction, allowing the inspection of electrical wiring, switches and other components without destructive disassembly. (*standard)

2.       125 amp, 120/240 VAC, single-phase, 3-wire service with 8-16 circuit breaker panel (*standard).

3.       Use copper wiring in surface mounted 1/2-inch (12.5 mm) minimum EMT conduit (*standard).

4.       Provide one 120-V GFCI power duplex receptacle every 8’ with tester (*standard).

5.       Wiremold (Optional) Series, one and two piece, multi channel non-metallic surface mounted raceway along front wall, above or below scorer’s table, outlets on 4’ centers, typical.

G.       Indoor Lighting Fixtures:

1.       Provide quantity of fixtures required to maintain the following illumination level:

** NOTE TO SPECIFIER **  Select the lighting levels required from following paragraphs and delete those not required.

a.       20 foot-candles.

b.       30 foot-candles.

c.       50 foot-candles (*standard).

** NOTE TO SPECIFIER **  Select the light fixture(s) required from following paragraphs and delete those not required.

2.       Ceiling-mounted fluorescent light fixture(s) 48 inches (1200 mm) long with two 32-W / T-8 lamps (*standard).

3.       Hi Abuse Fixture, Linear Fluorescent 40 Watts, Lamp Quantity 2, 120 V. Length 49.38 inches, width 9.25 inches, depth 3.38 inches, white, cold weather.

4.       Provide single-pole switch mounted adjacent to door to control lighting fixtures (*standard).

5.       Drop ceiling Troffer fixtures.

a.       24” x 24” - 32-W / T-8 lamps.

b.       24” x 48” – 32 W / T-8 lamps.

6.       Exit Signs:

a.       Exit signs shall be clearly marked. In the event of electrical power outage during use or occupancy in the press box, the exit signs will illuminate.

H.       Outdoor Lighting Fixtures:

1.       Provide quantity of fixtures required to maintain the following illumination level:

** NOTE TO SPECIFIER **  Select the lighting levels required from following paragraphs and delete those not required.

a.       20 foot-candles.

b.       30 foot-candles.

c.       50 foot-candles.

** NOTE TO SPECIFIER **  Select the light fixture(s) required from following paragraphs and delete those not required.

2.       Hi Abuse Fixture, Linear Fluorescent 40 Watts, Lamp Quantity 2, 120 V. Length 49.38 inches, width 9.25 inches, depth 3.38 inches, white, cold weather.

3.       Flood light, QTZ, RAB QF500W 120V, White.

4.       Flood light, QTZ, RAB QF500W 120V, Bronze.

** NOTE TO SPECIFIER **  Select the switch required from following paragraphs and delete those not required.

5.       Provide single-pole switch mounted adjacent to door to control lighting fixtures.

6.       Provide photoelectric controller.

** NOTE TO SPECIFIER **  Select the heating unit required from following paragraphs and delete those not required.

I.       Heating Unit: Wall-mounted, thermostatically controlled:

1.       110V, 1500W, 5120 Btu, electric heater with fan-forced operation, Enclose heater in enameled steel cabinet (*standard).

2.       230 /208V, 13,000/10,000 Btu, electric fan force, surface mounted electric heater.

** NOTE TO SPECIFIER **  Select the air conditioning/ventilating equipment required from following paragraphs and delete those not required.

J.       Thru-wall Air Conditioning:

1.       9,900 Btu, 110V.

2.       9,900 Btu, high mount, 110V.

K.       Thru-wall Heating/Air Conditioning:

1.       11,600/11,400 btu with electric heat 230/208V.

L.       Roof mount Air Conditioning:

1.       13,500 Btu, 110V.

M.       Roof mount Heating/Air Conditioning:

1.       13,500 Btu with 5,600 btu electric heat, 110V.

N.       Wall Exhaust Fan:

1.       Duct diameter 10-3/8 Inches.

2.       Motor 120 V, 1625 RPM, 1.7 amps, with air flow @ 0.000 inch static pressure 480.

O.       Scorer’s Table:

1.       Full length, 18” – 24” deep by 3/4" White “Melamine” counter top with drop wire grommets at receptacle locations (*standard).

2.       Full length, 18” – 24” deep by 16ga Stainless Steel counter top with drop wire grommets at receptacle locations.

P.       Storage Drawers:

** NOTE TO SPECIFIER **  Select the storage drawer(s) required from following paragraphs and delete those not required.

1.       Locking storage drawer, workbench mounted, 6-5/8 inches high, 20 inches deep, 17-1/4 inches wide.

Q.       Partition Walls with Interior Doors:

1.       Partition wall to separate the unit into two or more segmented  rooms:

a.       Home and Away.

b.       Home, Away and Announcer.

c.       Home, Away, Announcer and Press.

** NOTE TO SPECIFIER **  Select the restroom package required from following paragraphs and delete those not required.

R.       Restrooms:

1.       ADA restroom package provided with following items wired and installed:

a.       Lighting with wall switch.

b.       Thru wall exhaust fan.

c.       Heater: Wall mounted electric with fan forced operation, 1500w/5120 BTU, thermostat in enamel coated 20 ga steel cabinet.

** NOTE TO SPECIFIER ** Note that fixtures are supplied only for installation in the field.

d.       Supplied Fixtures:

          1) ADA elongated toilet

          2) ADA wall mounted lavatory

          3) One 36 inch grab bar

          4) One 42 inch grab bar

          5) One Toilet tissue holder

2.       Standard restroom package (non-ADA) provided with following items wired and installed.

a.       Lighting with wall switch

b.       One thru wall exhaust fan

c.       One Heater: shall be wall mounted electric with fan forced operation, 1500w/5120 BTU thermostat in an enamel coated 20 ga steel cabinet.

** NOTE TO SPECIFIER ** Note that fixtures are supplied only for installation in the field.

3.       Supplied Fixtures:

a.       ADA elongated toilet

b.       ADA wall mounted lavatory

c.       One Toilet tissue holder

2.5 FABRICATION

A.       Fabricate factory built, prefabricated Press Box completely in factory.

B.       Preglaze windows and doors at factory.

C.       Prewire factory built, prefabricated structures and shelters at factory, ready for connection to service at Project site.

D.       Separate dissimilar materials using nonconductive tape, paint, or other material not visible in finished work.

E.       Fabricate factory built, prefabricated structures and shelters for forklift unloading under base of booth with forklift pockets in base of booth or welded in place concealed lifting lugs at roof that are suitable for placement of the structure on prepared foundations.

PART 3 EXECUTION

3.1 EXAMINATION

A.       Examine supporting foundations for compliance with manufacturer's requirements, including installation tolerances and other conditions affecting performance of supporting members.

B.       Check installed anchor bolts for accuracy. Verify that bearing surfaces are ready to receive the work.

** NOTE TO SPECIFIER **  Select the following paragraph if required. Delete if not required.

C.       Verify the rough-in of required mechanical and electrical services prior to placement of the structure.

D.       If preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.

3.2 PREPARATION

A.       Clean surfaces thoroughly prior to installation.

B.       Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.

3.3 INSTALLATION