Specifications
for Aluminum Buildings
Download in PDF form
Download as a Microsoft Word Document
This MANU-SPEC®
utilizes the Construction Specifications Institute
(CSI) Manual of Practice, including Master-Format™,
Section-Format™ and Page-Format™. A MANU-SPEC
is a manufacturer-specific proprietary product specification
using the proprietary method of specifying applicable
to project specifications and master guide specifications.
Optional text indicated by brackets ( ); delete optional
text in final copy of specification.
This MANU-SPEC specifies portable
and mobile buildings, including prefabricated aluminum
and steel buildings and shelters, as manufactured
by AustinMohawk and Company, Inc. Revise MANU-SPEC
section number and title below to suit project requirements,
specification practices, and section content. Refer
to CSI Master-Format for other section numbers and
titles.
SECTION 13127
Portable & Mobile Buildings
(Prefabricated
Structures & Shelters)
PART 1 GENERAL
1.01 SUMMARY
|
A. |
Section Includes:
Portable and mobile buildings, including prefabricated
buildings and shelters
Specifier Note: Revise
above and below to suit project requirements.
AustinMohawk and Company, Inc. offers a variety
of portable and mobile buildings, including
guard booths, cashier and attendant booths,
petroleum kiosks, access control buildings,
utility buildings, smoking shelters, transit
shelters, waiting shelters, equipment shelters,
vestibules, and custom fabricated buildings. |
|
1. |
Types:
Types of prefabricated buildings and shelters
include:
a. ( Aluminum ) ( Steel ) buildings.
b. ( Aluminum ) ( Steel ) shelters.
Specifier Note: Revise
paragraph below to suit project requirements.
Add section numbers and titles per CSI Master-Format and specifier's
practice. |
| B. |
Related
Sections: Section(s) related to this section include:
|
|
1. |
Concrete
Pads: Division 3 Concrete Sections. |
| |
2. |
Electrical:
Division 16 Electrical Sections. |
1.02 SYSTEM DESCRIPTION
| A. |
Performance Requirements: Provide portable
and mobile buildings which have been manufactured,
fabricated and installed to withstand loads
from (Specify code/standard reference) and
to maintain performance criteria stated by manufacturer
without defects, damage, or failure.
Specifier Note: Article
below includes submittal of relevant data to
be furnished by Contractor either before, during,
or after construction. Coordinate this article
with Architect's and Contractor's duties and
responsibilities in Conditions of the Contract
and Division 1 Submittal Procedures Section.
|
1.03 SUBMITTALS
| A. |
General: Submit listed submittals in accordance
with Conditions of the Contract and Division
1 Submittal Procedures Section. |
| B. |
Product Data: Submit product data, including manufacturer's
SPEC-DATA® product sheets, for specified products. |
| C. |
Shop
Drawings: Submit shop drawings showing layout,
profiles and product components, including anchorage,
accessories, finish colors, patterns and textures. |
| D.
|
Samples:
Submit selection and verification samples for
finishes, colors and textures. |
| E. |
Quality
Assurance Submittals: Submit the following: |
| |
1. |
Certificates:
Product certificates signed by manufacturer certifying
materials comply with specified performance characteristics
and criteria, and physical requirements. |
| |
2.
|
Manufacturer's
Instructions: Manufacturer's installation instructions.
Specifier Note: Coordinate paragraph below
with Part 3 Field Quality Requirements Article
herein. Retain or delete as applicable. |
| |
3.
|
Manufacturer's
Field Reports: Manufacturer's field reports
specified herein. |
| F. |
Closeout
Submittals: Submit the following: |
| |
1.
|
Operation
and Maintenance Data: Operation and maintenance
data for installed products in accordance with
Division 1 Closeout Submittals (Maintenance Data
and Operation Data) Section. Include methods for
maintaining installed products, and precautions
against cleaning materials and methods detrimental
to finishes and performance. |
| 2. |
2.
Warranty: Warranty documents specified herein. |
1.04 QUALITY ASSURANCE
| A. |
A.
Installer Qualifications: Installer experienced
in performing work of this section who has specialized
in installation of work similar to that required
for this project.
Specifier Note: Paragraph
below should list obligations for compliance
with specific code requirements particular to
this section. General statements to comply with
a particular code are typically addressed in
Conditions of the Contract and Division 1 Regulatory
Requirements Section. Repetitive statements
should be avoided. |
| B.
|
Regulatory
Requirements: ( Specify applicable requirements
of regulatory agencies. ) |
1.05 DELIVERY, STORAGE & HANDLING
| A. |
General: Comply with Division 1
Product Requirements Sections |
| B. |
Ordering:
Comply with manufacturer's ordering instructions
and lead time requirements to avoid construction
delays. |
| C. |
Delivery: Deliver materials in manufacturer's
original, unopened, undamaged containers with
identification labels intact. |
| |
1. |
Ship
building fully assembled, prewired and ready
for use upon delivery.
Specifier Note: Edit
article below to suit project requirements.
If substitutions are permitted, edit text below.
Add text to refer to Division 1 Project Requirements
(Product Substitutions Procedures) Section.
|
1.06 WARRANTY
| A. |
Project Warranty: Refer to Conditions
of the Contract for project warranty provisions. |
| B. |
Manufacturer's
Warranty: Submit, for Owner's acceptance, manufacturer's
standard warranty document executed by authorized
company official. Manufacturer's warranty is in
addition to, and not a limitation of, other rights
Owner may have under Contract Documents. |
| |
|
Specifier
Note: Coordinate paragraph below with manufacturer's
warranty requirements.
Warranty Period: 1 year commencing on Date of
Shipment.
|
PART 2 PRODUCTS
Specifier Note:
Retain article below for proprietary method specification.
Add product attributes, performance characteristics,
material standards, and descriptions as applicable.
Use of such phrases as “or equal" or “or
approved equal", or similar phrases may cause
ambiguity in specifications. Such phrases require
verification (procedural, legal, and regulatory) and
assignment of responsibility for determining “or
equal" products.
2.01 PORTABLE
AND MOBILE BUILDINGS
| A. |
Manufacturer: AustinMohawk and Company, Inc.
Specifier Note: Paragraph
below is an addition to CSI Section-Format and
a supplement to MANU-SPEC. Retain or delete
paragraph below per project requirements and
specifier's practice. |
| |
1. |
Contact:
2175 Beechgrove Place, Utica, NY 13501; Telephone:
(800) 765-3110, (315) 793-3000; Fax: (315) 793-9370. |
| B. |
Proprietary
Product(s)/System(s): Austin Portable and Mobile
Buildings: |
| |
1.
|
(
Aluminum ) ( Steel ) buildings. |
| 2. |
(
Aluminum ) ( Steel ) buildings.
Specifier Note: Edit
article below to suit project requirements.
If substitutions are permitted, edit text below.
Add text to refer to Division 1 Project Requirements
(Product Substitutions Procedures) Section.
|
2.02 PRODUCT SUBSTITUTIONS
| A. |
Substitutions:
No substitutions permitted. |
2.03 MANUFACTURED ALUMINUM BUILDINGS
A. General: Pre-assemble building
fabricated from low maintenance, lightweight corrosive
resistant aluminum (factory fabricated).
- Dimensions: (Specified Width)
x (Specified Length) and 90" - 93" Nominal
outside height. Interior dimension from floor to
ceiling shall be 83" (2108.2 mm).
- Frame Construction: Provide structural
framing of 6063-T6 aluminum alloy extrusions. Members
shall have a Quaker Bronze finish. Connections shall
be fastened internally to framing systems using
mechanical fasteners or MIG welded where necessary.
- Base/Floor: Floor structure shall
be layered assembly, 2" (50.8 mm) thick, 2
pieces 5/8" plywood laminated together with
a .032 mill finish aluminum underside and a finished
floor of nonskid aluminum tread plate. Base is mounted
to 2" or 4" tube/channel steel base frame
(when necessary).
- Lower Wall Panel: Exterior shall
be .032 Quaker Bronze aluminum, 3" (76.2 mm)
insulation and .032 interior aluminum. Overall thickness
of panel shall be 3" (76.2 mm).
- Ceiling: Interior ceiling shall
be foam core panel system providing smooth flat
interior, constructed from 24 ga prefinished white
steel with expanded polystyrene core.
- Roof: Constructed using galvanized
20 ga, G-90 interlocking pan sections. Sections
are 3" (76.2 mm) high varying widths able to
support minimum of 50 psf (2394 Pa) live load. Roof
drains into full-perimeter gutter system.
- Windows: Fixed windows shall be
single pane 1/8" (3.18 mm) clear tempered safety
glass. Sliding windows shall have aluminum frame
and 1/8" (3.18mm) clear tempered safety glass,
insect screen, and locking device. Glass shall be
glazed within wall system extrusions and not fastened
to exterior wall. Glass sealed with concealed gasket
system.
- Door: Sliding door shall be extruded
aluminum frame, top hung style using heavy duty
ball bearing nylon tire with steel hub. Door shall
be supplied with jimmy-proof single cylinder deadlock.
- Electrical: Electrical shall be
wired according to N.E.C. Standards. Load center
shall be a 125 amp, 120/240 volt unit with 4 / 8
open circuits. Wiring shall be within surface mounted
EMT conduit lines, and included shall be a GFCI
duplex receptacle with tester
- Lighting: Lighting shall be a
twin fluorescent light with tube covers.
- Heat: Heating shall be wall mounted
electric with fan forced operation, 1500w/5120 BTU
and thermostat in an enamel coated 20 ga steel cabinet.
2.05 ALUMINUM SHELTERS
A. General: Pre-assembled shelter
fabricated from low maintenance, lightweight corrosive
resistant aluminum (factory fabricated).
- Dimensions: (Specified Width)
x (Specified Length), 88" (2235.2 mm) exterior
height and 83" (2108.2 mm) interior ceiling
height.
- Frame: 6063-T6 aluminum alloy extrusions
with standard QUAKER BRONZE finish. Framing assembled using internally
located mechanical fasteners. Exposed fasteners
on framing system are not acceptable.
- Roof: Constructed using galvanized
20 gauge, G-90 interlocking pan sections. Sections
are 3" (76.2 mm) high varying widths able to
support minimum of 50 psf (2394 Pa) live load. Roof
drains into full perimeter gutter system.
- Ceiling: Interior ceiling is
a foam core panel system providing smooth flat interior.
Constructed from 24 gauge prefinished white steel
with expanded polystyrene core, able to support
optional lighting or heat panels.
- Windows: Fixed windows are single
pane 3/16" (4.76 mm) clear tempered safety
glass, glazed within wall system extrusions and
not fastened to exterior wall. Glass sealed with
concealed gasket system.
- Lower Wall Section: (Optional)
.032 QUAKER BRONZE aluminum on exterior and interior
with expanded polystyrene core.
- Electrical: OPTIONAL ELECTRICAL
ITEMS TO BE INSTALLED BY OTHERS.
|
|
 |
|
PART 2 PRODUCTS (CONT.)
2.06 STEEL
BUILDINGS
A. General: Pre-Assembled
building of steel construction.
- Dimensions: (Specified Width)
x (Specified Length) and 96" (2438.4) norminal
in height.
- Frame: Framing shall be 14 GA
(1.78 mm) mechanical tube. Seams shall be MIG welded.
- Base/Floor: Building to typically
be constructed on a 4" galvanized mechanical
tube frame. Floor assembly to be 1" (25.4 mm)
thick comprised of galvanized steel under-side,
3/4" plywood and aluminum tread plate finished
floor.
- Wall Panels: Wallpanels shall
be 18 ga exterior, 2" (50.8 mm) or E.P.S. insulation,
and a 18 ga inside face. Panels shall be galvanized
and shall be MIG welded into place.
- Ceiling: Interior ceiling shall
be foam core panel system providing smooth flat
interior. Constructed from 24 ga prefinished white
steel with expanded polystyrene core.
- Roof: Constructed using galvanized
20 gauge, G-90 interlocking pan sections. Sections
are 3" (76.2 mm) high varying widths able to
support minumum of 50 psf (2394 Pa) live load. Roof
drains into full perimeter gutter system.
- Finish: Exterior surfaces shall
be smooth and flat with no visible blemishes. Surfaces
shall be painted using an epoxy/urethane prime to
paint system designed to withstand salt spray and
freze thaw testing.
- Windows: Fixed windows shall be
1/8" (3.18 mm) clear tempered safety glass.
Sliding and cashier windows shall be 1/8" (3.18
mm) clear tempered safety glass. Window frames shall
be anodized aluminum. Moving windows shall be supplied
with insect screen and locking device.
- Door: Sliding door shall be extruded
aluminum frame, top hung style using an overhead
track and heavy duty ball bearing nylon tires with
steel hub. Door shall be supplied with mortise lock
and hook bolt.
- Electrical: Electrical shall be
wired acording to N.E.C. Standards. Load center
shall be a 125 Amp, 120/240 volt unit with 8/16
open circuits. Wiring shall be within surface mounted
EMT conduit. (1) GFCI duplex receptacle with tester
is used as an outlet.
- Lighting shall be a twin fluorescent
light with tube covers.
- Heat: Heating will be wall mounted
electric with fan forced operation. 1500w/5120 BTU
and thermostat in an enamel coated 20 ga steel cabinet.
2.07 STEEL SHELTERS
B. Shelter: Constructed from high
strength structural tubing.
- Dimensions: (Specified Width)
x (Specified Length) having a 7' 6" (2438.4
mm) interior ceiling height.
- Frame: Framing shall be 14 ga
(1.78 mm) mechanical steel tube. Entire framing
system shall be MIG welded.
- Finish: Exterior surfaces shall
be smooth and flat with no visible blemishes. Surfaces
shall be painted using an epoxy/urethane prime to
paint system designed to withstand salt spray and
freeze thaw testing.
- Roof: Constructed using galvanized
20 gauge, G-90 interlocking pan sections. Sections
are 3" (76.2 mm) high varying widths able to
support minimum of 50 psf (2394 Pa) live load. Roof
drains into full perimeter gutter system.
- Ceiling: Interior ceiling shall
be foam core panel system providing smooth flat
interior. Constructed from 24 gauge prefinished
white steel with expanded polystyrene core and able
to support optional lighting or heat panels.
- Windows: Fixed windows shall be
single pane 3/16" (4.76mm) minimum clear tempered
safety glass. Glass shall be framed to shelter using
clear anodized aluminum framing system, with no
exterior exposed fasteners.
- Lower Wall Panels: (Optional)
Wall panels shall be 18 ga exterior, 3" (76.2mm)
of R-12 insulation, and a 18 ga inside face. Panels
shall be galvanized and shall be MIG welded into
place.
- Anchoring: Shelter installation
requires concrete pad 6" minimum thickness
and 12" minimum larger than shelter in both
length and width dimensions. Shelter to be anchored
to pad using height adjustable steel base plates
and anchored down using 1/2" minimum expansion
anchors.
2.08 ALUMINUM & STEEL SHELTERS OPTIONS
| A. |
Shelter Options: Provide shelter
as follows: |
| |
1. |
Color:
a. Aluminum Shelters: Quaker Bronze as a standard.
Any custom color is available as an option.
b. Steel Shelters: Soft black as a standard. Any
custom color is available as an option. |
| |
2. |
Glazing: (3/16" (4.76 mm) tempered safety
glass) (.1875 & .220 polycarbonate) (tinting
gray or bronze). |
| |
3. |
Lighting:
Twin bulb fluorescent fixtures. |
| |
4. |
Venting: Switch operated
wall fans. |
| |
5. |
Benches: 6', 8',10'
and 15' (1.8, 2.4, 3 and 5 m) pedestal mounted
mill Finish Aluminum. Installed directly to concrete
pad with expansion anchors. |
2.09 RELATED MATERIALS
| A. |
Related Materials:
Refer to other sections listed in Related Sections
for related materials. |
2.10 SOURCE QUALITY
| A. |
Source Quality:
Obtain portable and mobile buildings products
from a single manufacturer. |
PART 3
EXECUTION
Specifier Note:
Article below is an addition to CSI Section-Format
and a supplement to MANU-SPEC. Revise article below
to suit project requirements and specifier's practice.
3.01 MANUFACTURER'S INSTRUCTIONS
A.
|
Compliance:
Comply with manufacturer's product data, including
product technical bulletins, product catalog installation
instructions, and product carton instructions
for installation. |
3.02 EXAMINATION
| A. |
Site Verification
of Conditions: Verify substrate conditions (which
have been previously installed under other sections)
are acceptable for product installation in accordance
with manufacturer's instructions.
Specifier Note: Coordinate
article below with manufacturer's recommended
installation details and requirements. |
3.03 INSTALLATION
| A. |
Portable and Mobile Building Installation: |
| |
1. |
General:
Install building structure true to line, level,
plumb, rigid, and secure. Level base plates to
true plane with full bearing to support structure,
set in-place with anchor bolts as recommended
by building manufacturer. |
| |
2. |
Building
Anchoring: Install building on concrete pad 4"
(101.6 mm) minimum thickness and 12" (304.8
mm) minimum larger than building in both length
and width. Anchor building to pad using aluminum
boots and factory supplied expansion anchors. |
| |
3. |
Aluminum
Shelter Anchoring: Install shelter on concrete
pad 6" (152.4 mm) minimum thickness and 18"
(457.2 mm) minimum larger than shelter in both
length and width. Anchor shelter to pad using
height adjustable aluminum base plates and anchored
down using 1/4" (6.35 mm) min. expansion
anchors. |
| |
4. |
Steel
Shelter Anchoring: Install shelter on concrete
pad 6" (152.4 mm) minimum thickness and 18"
(457.2 mm) minimum larger than shelter in both
length and width. Anchor shelter to pad using
height adjustable steel base plates and anchored
down using _" (12.7 mm) min. expansion anchors. |
| B. |
Interface
with Other Work: (Specify applicable requirements
for interface with other work.) |
| C. |
Related
Products Installation: Refer to other sections
listed in Related Sections for related products
installation. |
3.04 FIELD QUALITY REQUIREMENTS
Specifier
Note: Edit paragraph below. Establish number and duration
of periodic site visits with Owner and manufacturer,
and specify below. Consult with manufacturer for services
required. Coordinate paragraph below with Division
1 Quality Assurance Section and Part 1 Quality Assurance
Submittals herein. Delete if manufacturer's field
service not required.
| A. |
Manufacturer's
Field Services: Upon Owner's request, provide
manufacturer's field service consisting of product
use recommendations and periodic site visit for
inspection of product installation in accordance
with manufacturer's instructions. |
| |
1. |
Site
Visits: (Specify number and duration of periodic
site visits.) |
3.05 CLEANING
| A. |
Cleaning:
Remove temporary coverings and protection of adjacent
work areas. Repair or replace damaged installed
products. Clean installed products in accordance
with manufacturer's instructions prior to owner's
acceptance. Remove construction debris from project
site and legally dispose of debris. |
3.06 PROTECTION
| A. |
Protection:
Protect installed product and finish surfaces
from damage during construction. |
|
|