Specifications for Steel Buildings
|
 |
|
New SpecWizard by arcat Just click the wizard to create your own custom spec! |
** NOTE TO SPECIFIER ** Austin Mohawk and Company, Inc.; Prefabricated
or factory-built structures.
.
This section is based on the
products ofAustin Mohawk and Company, Inc., which is located at:
2175 Beechgrove Place
Utica, NY 13501
Toll Free Tel: 800-765-3110
Tel: 315-793-3000
Fax: 315-793-9370
Email: info@austinmohawk.com
Web: www.austinmohawk.com
[ Click Here ] for additional information.
Austin Mohawk, Inc. was created in
2004 with the merging of Austin Fabricating, Inc., (buildings and shelters) and
Mohawk Manufacturing, Inc. (canopies), two longtime sister companies. In their
respective industries, each was among the oldest and most well respected
manufacturers. Together, we expect to bring an even stronger and more integrated
product line to our customers.
Austin Mohawk has spent more than
80 years building superior quality, prefabricated metal structures. Our product
lineup includes pre-manufactured buildings, shelters, and metal canopies. Prefabricated or
factory-built structures have significant advantages over site-built
constructionincluding economy, speed, quality, and flexibility. Our
prefabricated metal buildings and booths can be custom built in aluminum or
steel. From security buildings to cashier booths to parking booths, our custom
built booths and buildings are modular, functional, and aesthetically pleasing.
Our metal canopies and walkway covers are designed, fabricated and shipped for
on-site erection.
.
SECTION 13129 - PREFABRICATED METAL
BUILDINGS AND SHELTERS, Copyright 2006, ARCAT, 1nc.
PART 1 GENERAL
1.1 SECTION
INCLUDES
** NOTE TO SPECIFIER **
Delete items below not required for project.
A. Prefabricated
Steel Buildings.
1.2 RELATED
SECTIONS
** NOTE TO SPECIFIER **
Delete any sections below not relevant to this project; add others as
required.
A. Section
03300 - Cast-In-Place Concrete: Concrete pad, foundations and anchor bolts.
B. Section
02870 - Bollards: Metal, concrete and stone bollards.
C. Section
05500 - Metal Fabrications.
D. Section
08710 - Door Hardware.
E. Section
07900 - Joint Sealers.
F. Division
15 - Plumbing: Plumbing services
and connections.
G. Division
16 - Electrical: Electrical power
service and wiring connections.
1.3 REFERENCES
** NOTE TO SPECIFIER **
Delete references from the list below that are not actually required by
the text of the edited section.
A. ASTM
A 513 - Standard Specification for Electric-Resistance-Welded Carbon And Alloy
Steel Mechanical Tubing.
B. ASTM
A 653/A - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or
Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.
C. ASTM
A 1008/A - Standard Specification for Steel Bars, Carbon and Alloy, Cold-
Finished.
D. ASTM
B 209 - Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate.
E. ASTM
B 221 - Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars,
Rods, Wire, Profiles, and Tubes.
F. ASTM
B 632/B 632M - Standard Specification For Aluminum-Alloy Rolled Tread Plate.
G. ASTM
C-578 - Standard Specification For Rigid, Cellular Polystyrene Thermal Insulation.
H. ASTM
C 1048 - Standard Specification for Heat-Treated Flat Glass - Kind Hs, Kind Ft
Coated and Uncoated Glass.
I. ASCE
7 - Minimum Design Loads for Buildings and Other Structures
J. APA
PRP-108 or PFS PRP-133 - Performance Standards and Policies for Structural-Use
Panels.
K. ICC/ANSI
A117.1 - Accessible and Usable Buildings and Facilities.
L. NFPA
70 - National Electric Code.
M. UL
752 - Standard for Bullet Resisting Equipment.
N. IBC
- International Building Code.
O. NIJ
National Institute of Justice (NIJ) Standard 0101.04 (Ballistic Resistance of
Personal Body Armor).
1.4 DESIGN
REQUIREMENTS
** NOTE TO SPECIFIER ** Edit
as required to suit project requirements. Standard loads are specified below,
consult with manufacturer for requirements that exceed those specified as
follows.
A. Provide
factory built, prefabricated structures and shelters capable of withstanding
the effects of gravity loads and the following loads and stresses within limits
and under conditions indicated.
B. Wind
Loads: Determine loads based on the
following minimum design wind pressures:
** NOTE TO SPECIFIER **
Select one of the following two paragraphs and delete the one not
required.
1. Uniform
pressure of 50 lbf/sq ft, acting inward or outward (standard).
2. Uniform
pressure as indicated on Drawings.
3. Wind
Load:
** NOTE TO SPECIFIER **
Select one of the following two paragraphs and delete the one not
required.
a. Buildings: 120 mph (2000 IBC Exp. C). (standard).
b. Shelters: 90 mph. (standard).
4. Snow
Loads: 50 lbf/sq ft. (standard).
C. Seismic
Performance: Provide factory built,
prefabricated structures and shelters capable of withstanding the effects of
earthquake motions determined according to:
1. ASCE
7, "Minimum Design Loads for Buildings and Other Structures": Section
9, "Earthquake Loads".
D. Thermal
Movements: Provide factory built,
prefabricated structures and shelters that allow for thermal movements
resulting from the following maximum change (range) in ambient and surface
temperatures by preventing buckling, opening of joints, overstressing of components,
failure of joint sealants, failure of connections, and other detrimental
effects. Base engineering
calculation on surface temperatures of materials due to both solar heat gain
and nighttime-sky heat loss.
1. Temperature
Change (Range): 120 deg F (67 deg
C), ambient; 180 deg F (100 deg C), material surfaces.
E. Electrical
Devices: Devices UL listed with wiring bearing UL classification and conforming
to the current NEC,
** NOTE TO SPECIFIER ** Adherence to applicable state and local codes is
the responsibility of the Owner. For modular buildings, several state codes
have requirements for third party design approval and inspection for compliance
and/or the provision of P.E. stamped drawings. Verify the requirements for your
jurisdiction. These costs, if applicable,
vary significantly between states and are available from building
manufacturer at additional cost. Typically metal buildings on Federal
Reservations do not require State or Local approvals. Metal shelters do not
generally require design approval and inspection for compliance. Delete the
following Performance Requirement paragraph if not required.
1.5 PERFORMANCE
REQUIREMENTS
** NOTE TO SPECIFIER ** The following states generally require third
party design approval and inspection for modular buildings unless the project
is a US Government or Agency job. Delete if not required:
Alabama, Arizona, California,
Colorado, Connecticut, Florida, Georgia, Idaho, Indiana, Iowa, Kentucky,
Louisiana, Maryland, Massachusetts, Michigan, Minnesota, Missouri, New
Hampshire, New Jersey, New Mexico, Nevada, North Carolina, Ohio, Oregon,
Pennsylvania (if building will be occupied by more than 4 people), Rhode
Island, South Carolina, Tennessee, Texas, Virginia, Washington, Wisconsin.
** NOTE TO SPECIFIER ** If a professional
engineers' stamp is required on the shop drawings for metal buildings or
shelters, please designate state.
Delete if not required.
Alabama, Alaska, Arizona, Arkansas,
California, Colorado, Connecticut, Delaware, District of Columbia, Florida,
Georgia, Hawaii, Idaho, Illinois, Indiana, Iowa, Kansas, Kentucky, Louisiana,
Maine, Maryland, Massachusetts, Michigan, Minnesota, Mississippi, Missouri,
Montana, Nebraska, Nevada, New Hampshire, New Jersey, New Mexico, New York,
North Carolina, North Dakota, Ohio, Oklahoma, Oregon, Pennsylvania, Puerto
Rico, Rhode Island, South Carolina, South Dakota, Tennessee, Texas, Utah,
Vermont, Virginia, Virgin Islands, Washington, West Virginia, Wisconsin,
Wyoming.
A. Cooperate
with regulatory agency or authority and provide data as requested by authority
having jurisdiction.
1.6 SUBMITTALS
A. Submit
under provisions of Section 01300.
B. Product
Data: Manufacturer's
data sheets on each product to be used, including:
1. Construction
details, material descriptions, dimensions of individual components and
profiles, and finishes.
2. Preparation
instructions and recommendations.
3. Storage
and handling requirements and recommendations.
4. Installation
methods.
C. Shop
Drawings: Include plans, elevations, sections, details, and attachments to
other work.
D. Selection
Samples: For each finish product
specified, two complete sets of color chips representing manufacturer's full
range of available colors and patterns.
E. Certificates: Product certificates signed by the
manufacturer certifying material compliance with specified performance
characteristics and criteria, and physical requirements.
F. Warranty
documents specified herein.
1.7 QUALITY
ASSURANCE
A. Manufacturer
Qualifications: Company specializing in manufacturing prefabricated structures
and shelters with a minimum documented experience of twenty years and with a
quality assurance program utilizing an independent third party quality control
firm with a 5-stage, 35 step, quality inspection for each system.
B. Preinstallation
Meetings: Conduct meetings to
verify project requirements, substrate conditions, utility connections,
manufacturer's installation instructions, and warranty requirements. Comply with Division 1 requirements.
1.8 DELIVERY,
STORAGE, AND HANDLING
A. Store
products in manufacturer's unopened packaging until ready for installation.
B. Protect
all components and accessories from corrosion, deformation, damage and
deterioration when stored at job site.
Keep materials free from dirt and foreign matter.
1.9 PROJECT
CONDITIONS
A. Maintain
environmental conditions (temperature, humidity, and ventilation) within limits
recommended by manufacturer for optimum results. Do not install products under
environmental conditions outside manufacturer's absolute limits.
1.10 WARRANTY
A. Provide
the manufacturer's 5 year limited warranty on anodized aluminum surfaces
against oxidation and the manufacturers 20 year limited warranty against
peeling, flaking and chipping of deck and fascia when properly maintained.
** NOTE TO SPECIFIER **
Delete the following paragraph if the stated accessory items are not
required.
B. Provide
manufacturer's warrantees on all accessory items provided such as, but not
limited to, air conditioning, lights, and heating units.
PART 2 PRODUCTS
2.1 MANUFACTURERS
A. Acceptable
Manufacturer: Austin Mohawk and Company, Inc., which is located at: 2175
Beechgrove Place ; Utica, NY 13501;
Toll Free Tel: 800-765-3110; Tel: 315-793-3000; Fax: 315-793-9370; Email: info@austinmohawk.com;
Web: www.austinmohawk.com
** NOTE TO SPECIFIER **
Delete one of the following two paragraphs; coordinate with requirements
of Division 1 section on product options and substitutions.
B. Substitutions: Not permitted.
C. Requests
for substitutions will be considered in accordance with provisions of Section
01600.
2.2 MATERIALS
A. Aluminum: Alloy and temper recommended by
manufacturer for type of use and finish specified, and as follows:
1. Sheet: ASTM B 209.
2. Extruded
Shapes: ASTM B 221.
3. Rolled
Tread Plate: ASTM B 632/B 632M,
Alloy 6061-T4 or 6061-T6.
B. Cold-Rolled
Steel Sheet: ASTM A 1008/A,
Commercial Steel (CS), Type B.
C. Zinc-Coated
(Galvanized) Steel Sheet: ASTM A
653/A, commercial quality, G90 (Z275) coating designation; mill phosphatized.
D. Aluminum
Treadplate: 1/8-inch aluminum plate conforming to ASTM B 209.
E. Steel
Mechanical Tubing: ASTM A 513,
welded steel mechanical tubing.
F. Expanded
Polystyrene (EPS) Core: Minimum of .95 pcf complying with ASTM C-578 Type 1.
G. Oriented
Strand Board (OSB): Standard Grade;
minimum physical properties conforming to APA PRP-108.
H. Clear
Tempered Float Glass: ASTM
C 1048, Kind FT, Condition A, Type I, Class 1, Quality q3.
I. Ballistics-Resistant
Glazing: Comply with requirements
of UL 752 and/or NIJ.
J. Anchorages: Anchor bolts, as specified in Section
03300.
2.3 PREFABRICATED
STEEL BUILDINGS
A. Size:
** NOTE TO SPECIFIER **
Select the size required from the following paragraphs and delete those
not required. The maximum shipping width for custom sizes is 16 feet.
1. 3
feet by 4 feet.
2. 4
feet by 4 feet.
3. 4
feet by 5 feet.
4. 4
feet by 6 feet.
5. 4
feet by 7 feet.
6. 4
feet by 8 feet.
7. 4
feet by 9 feet.
8. 4
feet by 10 feet.
9. 5
feet by 5 feet.
10. 5
feet by 6 feet.
11. 5
feet by 7 feet.
12. 5
feet by 8 feet.
13. 5
feet by 9 feet.
14. 5
feet by 10 feet.
15. 5
feet 6 inches by 7 feet 6 inches (minimum ADA size).
16. 6
feet by 6 feet.
17. 6
feet by 8 feet.
18. 6
feet by 10 feet.
19. 6
feet by 12 feet.
20. 6
feet by 15 feet.
21. 8
feet by 8 feet.
22. 8
feet by 10 feet.
23. 8
feet by 12 feet.
24. 8
feet by 14 feet.
25. 8
feet by 16 feet.
26. 10
feet by 10 feet.
27. 10
feet by 12 feet.
28. 10
feet by 14 feet.
29. 10
feet by 16 feet.
30. 10
feet by 20 feet.
31. 12
feet by 12 feet.
32. 12
feet by 14 feet.
33. 12
feet by 16 feet.
34. 12
feet by 18 feet.
35. 12
feet by 20 feet.
36. Custom:
_____ by _____.
B. Height:
Nominal outside height 96 inches (2438.4 mm). Interior floor to ceiling height
88 inches (22358 mm).
C. Prefabricated
with 14 gauge (1.78 mm) mechanical tube, welded framing system. Exterior smooth
and flat with no exposed fasteners on building exterior.
1. Building
Style:
** NOTE TO SPECIFIER **
Select the building style required from the following paragraphs and
delete those not required. Coordinate custom styles with Austin Mohawk.
a. Alford.
b. Stainless
Peer.
c. Fort
Bull.
d. Classic.
e. Defiance.
f. Statesman.
g. Sentry.
h. Tru
View.
i. Ramsey.
j. Soft
Corner.
k. Easy
Round.
l. Heavy
Duty.
m. Sharpline.
n. Governor.
o. College
Square.
p. Masonic.
q. Columbia.
r. Colonial.
s. Newtown.
t. Highlight.
u. Avis.
v. Galveston.
w. Louisville
Special.
x. Poolville.
y. Mobil.
z. McDonalds.
aa. Pro-Tech.
bb. Waverly.
cc. Hobart.
dd. Classic
w/Camera Deck.
ee. St.
James.
ff. Dutch
Door.
gg. Shell.
hh. Hess.
ii. Roll-Up.
jj. American
Roll-Up.
kk. Pro
Ball.
ll. Custom
as indicated on Drawings.
2. Doors:
** NOTE TO SPECIFIER **
Select the door types required from the following paragraphs and delete
those not required. Single sliding door one side is standard.
a. Sliding
door on one side.
b. Sliding
doors on both sides.
c. Swinging
door(s).
d. As
indicated on Drawings.
3. Windows:
** NOTE TO SPECIFIER **
Select the window types required from the following paragraphs and
delete those not required. Fixed widows with one horizontal sliding window are
standard.
a. Fixed
windows and one slider with insect screen and positive locking device..
b. Additional
fixed window(s).
c. Additional
horizontal sliding window(s).
d. Vertical
Sliding Window(s).
e. One
Cashier Window.
f. As
indicated on Drawings.
g. Glazing:
** NOTE TO SPECIFIER ** Select the glazing required and delete those not
required. Clear tempered glass, 1/8 inch, is standard.
1) 1/8
inch (3 mm) thick, clear tempered safety glass.
2) 3/16
inch (4.5 mm) thick, clear tempered safety glass.
3) 1/4
inch (6 mm) thick, clear tempered safety glass.
4) 3/4
inch (19 mm) thick, insulated, clear tempered safety glass.
5) 1/4
inch (6 mm) thick, clear polycarbonate.
6) With
tint, grey, bronze, green.
7) Low
E.
8) Ballistic
protection as specified.
9) As
indicated on Drawings.
4. Roof
Type:
** NOTE TO SPECIFIER **
Select the roof type required from the following paragraphs and delete
those not required. Flat deck roof is standard.
a. Flat
Deck Roof with 3 inch high overlapping deck pans
b. Standing
Seam Hip
c. Expanded
Metal Hip
d. Cedar
Shingle Hip
e. Asphalt
Shingle Hip
f. Standing
Seam Mansard
g. Cedar
Shingle Mansard
h. Asphalt
Mansard
i. Optional
Decorative Sill Reveal
j. Optional
Decorative Corner Arches
k. As
Indicated on Drawing
5. Roof
Overhang:
** NOTE TO SPECIFIER **
Select the overhang required from the following paragraphs and delete
those not required.
a. 4
inch overhang (standard).
b. 6
inch overhang.
c. 12
inch overhang.
d. 24
inch overhang.
e. As
indicated on drawing.
D. Frame
Construction: Framing shall be 14 gauge (1.78 mm) or heavier mechanical tube.
All joints shall be MIG welded.
1. Finish:
Exterior shall have a manufacturer's epoxy primer with a urethane finish as
follows:
** NOTE TO SPECIFIER **
Select the color required from the following paragraphs and delete those
not required. Custom colors are available at additional cost.
a. Color
as selected from manufacturers standard colors.
b. Custom
color as selected by the Architect.
E. Base/Floor:
Finished floor of nonskid aluminum tread plate. Floor is mounted to 2 inch to 4
inch (51 mm to 102 mm) tube/channel steel base frame.
F. Wall
Panel: Exterior face of manufacturers standard 16 gauge galvanized steel, an
E.P.S. insulation core and a 16 gauge galvanized steel interior face. Panels
shall be MIG welded into place.
1. Overall
thickness:
a. 2
inches (50.8 mm) R-10.
b. 3
inches (76.2 mm) R-12.
c. R-value
as indicated on drawing.
2. Finish:
Interior and exterior panel faces shall have a manufacturer's epoxy primer with
a urethane finish as follows:
** NOTE TO SPECIFIER **
Select the color required from the following paragraphs and delete those
not required. Custom colors are available at additional cost.
a. Color
as selected from manufacturers standard colors.
b. Custom
color as selected by the Architect.
G. Interior
Ceiling Panels: Prefinished steel, 24 gauge painted white with expanded
polystyrene core providing a smooth flat interior.
H. Roof:
Galvanized steel, 20 to 24 gauge, G-60 zinc coating, interlocking pan sections,
3 inches (76.2 mm) high varying widths and capable of supporting a minimum 40
psf (1915 Pa) live load. Roof drains into full perimeter gutter system.
** NOTE TO SPECIFIER **
Select the building accessories required from the following paragraphs
and delete the items not required. Coordinate the selection of doors and
ballistic windows with the selections identified in the previous building
paragraphs.
2.4 BUILDING
ACCESSORIES
A. Sliding
Doors: Horizontal sliding unit with extruded aluminum frame, top hung.
** NOTE TO SPECIFIER **
Select the paragraphs required and delete the ones not required.
1. 32
inches by 80 inches (812 mm by 2032 mm) half glass aluminum sliding door with
mortised laminated hook bolt lock capable of being keyed.
2. Glazing:
1/8 inch (3.18 mm) thick, clear tempered safety glass.
3. As
indicated on the Drawings.
B. Swinging
Doors: 1-3/4 inches (44 mm) thick, tubular-frame design.
** NOTE TO SPECIFIER **
Select the door required and delete the ones not required.
1. Commercial
Grade Aluminum Swing Door 36 inches by 80 inches (914 mm by 2032 mm) Half Glass
with mortised, laminated bolt lock with removable cylinder capable of being
keyed.
2. Commercial
Grade Aluminum Swing Door 36 inches by 80 inches (914 mm by 2032 mm). Full Glass with mortised, laminated bolt
lock with removable cylinder capable of being keyed.
3. Commercial
Grade Steel Swing Door 36 inches by 80 inches (914 mm by 2032 mm) with 12 inch
by 12 inch (305 mm by 305 mm) lite with steel single bore lever handle lockset
with keyed entry and interior thumb turn as indicated on drawing.
4. Commercial
Grade Steel Swing Door 36 inches by 80 inches (914 mm by 2032 mm). No Glass.
5. As
indicated on the Drawings.
C. Ballistic
Fixed Windows:
** NOTE TO SPECIFIER **
Select the ballistic resistant level required from the following
paragraphs and delete those not required.
1. Ballistic
resistant glazing, UL 752:
a. Level
I.
b. Level
II.
c. Level
III.
d. Level
IV.
e. Level
V.
f. Level
VI.
g. Level
VII.
h. Level
VIII.
i. NIJ
Level I.
j. NIJ
Level II.
k. NIJ
Level IIA.
l. NIJ
Level III.
m. NIJ
Level IIIA.
n. NIJ
Level IV.
2. Glazed
within an extruded aluminum exterior stop and an extruded aluminum interior
stop which are mechanically fastened to interior face of the window rough
openings.
3. Glass
sealed with butyl architectural glazing tape.
** NOTE TO SPECIFIER **
Ballistic resistant wall panels and doors are optional. Select the
ballistic resistant level required from the following paragraphs and delete
those not required. Delete if not required. Note: Steel buildings are built to all BR
Standards, Aluminum Buildings not available in Levels V - VIII.
D. Ballistic
Protection: Provide ballistic resistant wall panels, doors and glazing in
accordance with UL 752 to the following level:
1. Level
I.
2. Level
II.
3. Level
III.
4. Level
IV.
5. Level
V.
6. Level
VI.
7. Level
VII.
8. Level
VIII.
9. NIJ
Level I.
10. NIJ
Level II.
11. NIJ
Level IIA.
12. NIJ
Level III.
13. NIJ
Level IIIA.
14. NIJ
Level IV.
E. Electrical
Power Service: Provide in accordance with NEC Standards.
1. 125
amp, 120/240 VAC, single-phase, 3-wire service with 8-16 circuit breaker panel.
2. Use
copper wiring in surface mounted 1/2-inch (12.5 mm) minimum EMT conduit.
3. Provide
one 120-V GFCI power duplex receptacle with tester.
F. Indoor
Lighting Fixtures:
1. Ceiling-mounted
fluorescent light fixture(s) 48 inches (1200 mm) long with two 40-W lamps.
2. Provide
single-pole switch mounted adjacent to door to control lighting fixtures.
** NOTE TO SPECIFIER **
Outdoor fixtures are optional. Select if required or delete if not
required.
G. Outdoor
Lighting Fixtures:
** NOTE TO SPECIFIER **
Select the light fixture(s) required from following paragraphs and
delete those not required.
1. Hi
Abuse Fixture, Linear Fluorescent 40 Watts, Lamp Quantity 2, 120 V. Length
49.38 inches, width 9.25 inches, depth 3.38 inches, white, cold weather.
2. Flood
light, QTZ, RAB QF500W 120V, White.
3. Flood
light, QTZ, RAB QF500W 120V, Bronze.
** NOTE TO SPECIFIER **
Select the switch required from following paragraphs and delete those
not required.
4. Provide
single-pole switch mounted adjacent to door to control lighting fixtures.
5. Provide
photoelectric controller.
** NOTE TO SPECIFIER **
Select the heating unit required from following paragraphs and delete
those not required.
H. Heating
Unit: Wall-mounted, thermostatically controlled:
1. 110V,
1500W, 5120 Btu, electric heater with fan-forced operation, Enclose heater in
enameled steel cabinet.
2. 230
/208V, 13,000/10,000 Btu, electric fan force, surface mounted electric heater.
3. Infrared
Heater, 3.2KW, 60Hz 208V, current @ single phase 15.4 amp, current at three
phase 8.9 amp, BtuH 10922, beam pattern.
** NOTE TO SPECIFIER **
Select the air conditioning/ventilating equipment required from
following paragraphs and delete those not required.
I. Thru-wall
Air Conditioning:
1. 9,900
Btu, 110V.
2. 9,900
Btu, high mount, 110V.
J. Thru-wall
Heating/Air Conditioning:
1. 11,600/11,400
btu with electric heat 230/208V.
K. Roof
mount Air Conditioning:
1. 13,500
Btu, 110V.
L. Roof
mount Heating/Air Conditioning:
1. 13,500
Btu with 5,600 btu electric heat, 110V.
M. Wall
Exhaust Fan:
1. Duct
diameter 10-3/8 Inches.
2. Motor
120 V, 1625 RPM, 1.7 amps, with air flow @ 0.000 inch static pressure 480.
N. Storage
Drawers:
** NOTE TO SPECIFIER **
Select the storage drawer(s) required from following paragraphs and
delete those not required.
1. Thru-wall
transaction drawer, stainless steel housing with bullet resistant plastic
drawer, counter mounted. Ballistic resistant glazing set above the flat hood
portion of drawer. As drawer slides out the stainless steel front panel pivots
upward. Lexan lid stays closed when drawer is extended.
a. Counter
opening size: 14-1/2 inches wide by 17-1/8 inches deep by 5-3/4 inches high.
b. Drawer
extension: 9 inches.
c. Inside
dimensions of drawer: 12 inches wide by 14-5/8 inches deep by 3-5/8 inches
high.
2. Locking
storage drawer, workbench mounted, 6-5/8 inches high, 20 inches deep, 17-1/4
inches wide.
3. Locking
Cash Drawer, workbench mounted, 3.5 inches (89 mm) high, 16.3 inches (414 mm)
deep, 13 inches (330 mm) wide.
** NOTE TO SPECIFIER **
Select the restroom package required from following paragraphs and
delete those not required.
O. Restrooms:
1. Standard
restroom package (non-ADA) provided with following items wired and installed.
a. Lighting
with wall switch.
b. Thru
wall exhaust fan.
c. Heater:
Wall mounted electric with fan forced operation, 1500w/5120 BTU thermostat in
an enamel coated 20 gauge steel cabinet.
** NOTE TO SPECIFIER ** Note that fixtures can be installed or supplied only for installation in the
field. Select paragraph required and delete the one not required.
d. Fixtures
installed:
1) Elongated
toilet.
2) Wall
mounted lavatory.
3) One
Toilet tissue holder.
e. Supplied
fixtures for installation by others:
1) Elongated
toilet.
2) Wall
mounted lavatory.
3) One
Toilet tissue holder.
2. ADA
restroom package provided with following items wired and installed:
a. Lighting
with wall switch.
b. Thru
wall exhaust fan.
c. Heater:
Wall mounted electric with fan forced operation, 1500w/5120 BTU, thermostat in
an enamel coated 20 gauge steel cabinet.
** NOTE TO SPECIFIER ** Note that fixtures can be installed or supplied only for installation in the
field. Select paragraph required and delete the one not required.
d. Fixtures
installed:
1) ADA
elongated toilet.
2) ADA
wall mounted lavatory.
3) One
36 inch grab bar.
4) One
42 inch grab bar.
5) One
Toilet tissue holder.
e. Supplied
fixtures for installation by others:
1) ADA
elongated toilet.
2) ADA
wall mounted lavatory.
3) One
36 inch grab bar.
4) One
42 inch grab bar.
5) One
Toilet tissue holder.
2.5 FABRICATION
A. Fabricate
factory built, prefabricated structures and shelters completely in factory.
B. Preglaze
windows and doors at factory.
C. Prewire
factory built, prefabricated structures and shelters at factory, ready for
connection to service at Project site.
D. Separate
dissimilar materials using nonconductive tape, paint, or other material not
visible in finished work.
E. Fabricate
factory built, prefabricated structures and shelters for forklift unloading
under base of booth with forklift pockets in base of booth or welded in place
concealed lifting lugs at roof that are suitable for placement of the structure
on prepared foundations.
PART 3 EXECUTION
3.1 EXAMINATION
A. Examine
supporting foundations for compliance with manufacturer's requirements,
including installation tolerances and other conditions affecting performance of
supporting members.
B. Check
installed anchor bolts for accuracy. Verify that bearing surfaces are ready to
receive the work.
** NOTE TO SPECIFIER **
Select the following paragraph if required. Delete if not required.
C. Verify
the rough-in of required mechanical and electrical services prior to placement
of the structure.
D. If
preparation is the responsibility of another installer, notify Architect of
unsatisfactory preparation before proceeding.
3.2 PREPARATION
A. Clean
surfaces thoroughly prior to installation.
B. Prepare
surfaces using the methods recommended by the manufacturer for achieving the
best result for the substrate under the project conditions.
3.3 INSTALLATION
A. Install
in accordance with manufacturer's instructions.
B. Separate
dissimilar materials using nonconductive tape, paint, or other material not
visible in finished work.
C. Place
on prepared concrete foundations and slabs provided as specified under Section
03300.
D. Anchor
securely in place, allowing for required movement, including expansion and
contraction.
** NOTE TO SPECIFIER **
Select the following paragraphs if required. Delete if not required.
E. Connect
mechanical services as specified under Division 15.
F. Connect
electrical services as specified in Division 16.
3.4 PROTECTION
A. Protect
installed products until completion of project.
B. Touch-up,
repair or replace damaged products before Substantial Completion.
|